Sensor Wires
To Control
Board
Shield Ground
Drain Wire (less than 50 mm)
To
Sensor
OM-1008
WIRING OF SENSING DEVICES
Figure 7-1: Earth Bar Wiring
• Control wiring and power wiring must be run in
dedicated or separate earthed metal conduit, cable
trays, or trunking.
• Grounding requirements - The earth must be made
by solid metal to metal connections. The ground must
be good radio frequency earth. Ground wire should be
the same size as power wiring.
For maximum E.M.C. effectiveness, all humidity,
temperature and air flow controls should be wired
using multi-conductor shielded plenum-rated cable
with a drain wire for the shield. The drain wire should
be connected to the shield ground terminal with it's
length kept to less than 50 mm.
• When selecting a space to install the humidifier,
avoid areas close to sources of electromagnetic
emissions such as KVA transformers and variable
frequency drives.