The following pages contain information about the digital read-outs that VAPOR-LOGIC
®
communicates. Not all
the scrolled information appears in every system. This is dependent on the system configuration. A variety of
preset system conditions and programmable parameters that ultimately control the humidification system, as well
as a trouble-shooting guide to help you with operational procedures. The charts are organized based upon when
or why the information is communicated.
MAIN MENU
READ-OUT
MAIN MENU
DESCRIPTION
RANGE DEFAULT
AUTO
SCROLL
AUTO SCROLL
READ-OUT
"SET % RH SP" Room Set Point (1) 20-80% RH 35% yes
"DESIRED RH:%"
"ACTUAL RH: %"
"TRIM % RH" Trim Range (1)
±10% from
present set
point reading
No trim. no
"SET RH TR" Throttling Range (1) 2-20% RH 11% RH no
"SET HL RH SP"
Duct Set Point (VAV
Option) (2)
50-90% RH 70% RH yes
"MAX. HL RH:%"
"ACT. HL RH:%"
"TRIM HL %RH"
Trim High Limit Range
(2)
±10% from
present high
limit set point
reading
No trim. no
"TRIM TEMP"
Trim Temperature
Range (3)
±11°C from
present glass
temperature
reading
No trim. no
"SET ADS
INTERVAL"
Auto Drain Sequence
Interval (4)
1-99 hours 50 hours no
"SET ADS DUR"
Auto Drain Sequence
Duration (4)
1-30 minutes 8 minutes no
"SET AFS DUR"
Auto Flush Sequence
Duration (4)
1-30 minutes 8 minutes no
"SET SKIM DUR" Skim Time Duration 2-60 seconds 2 seconds no
"TIME TO ADS"
Time Until Auto Drain
Sequence (in hours,
minutes, seconds) (4)
1-99 hours 50 hours no
"TIME TO SRVE"
Time Until
Recommended
Service (in hours,
minutes, seconds) (4)
Counts down
from 2000
hours.
2000 hours no
MAIN MENU/AUTO SCROLL INFORMATION