48
TROUBLE-SHOOTING GUIDE
PROBLEM POSSIBLE CAUSE RECOMMENDED ACTION
HUNTING (con't.) Malfunctioning control system
(con't.)
Verify that 4 wire modular cable is isolated from power
wiring.
Air volume varying rapidly Stabilize.
Air temperature varying rapidly Stabilize ±1°C.
UNIT DOES NOT
PERFORM
AUTO-DRAIN
SEQUENCE
System may not have automatic
drain system
Inspect unit to verify that automatic drain valve was
furnished.
Drain fault, plugged drain valve
or plugged drain pipe
Clean drain valve piping.
Malfunctioning auto drain
sequence
Check VAPOR-LOGIC main menu settings and reset if
necessary.
No power to automatic drain
valve
Check if 24 VAC is present at VAPOR-LOGIC control
board terminals 18 & 19, and drain valve.
Defective automatic drain valve Valve should be replaced if voltage is present at valve
and it still does not open.
®