TROUBLE-SHOOTING GUIDE
PROBLEM POSSIBLE CAUSE RECOMMENDED ACTION
HUMIDITY ABOVE
DESIRED LEVEL
(con't.)
Humidity control input type
not the same as
VAPOR-LOGIC software
Check VAPOR-LOGIC control board connections J9,
J10 and J11. Consult DRI-STEEM.
HUMIDITY ABOVE
SET POINT
High entering relative
humidity
Dehumidify.
Unit oversized Consult DRI-STEEM.
Reduced air flow Check fans, dampers, VAV systems, etc.
Improperly located
humidistat or humidity
transmitters
Relocate using guidelines established in this manual.
(See page 5.)
Malfunctioning controls Check for incorrect supply voltage.
Check for incorrect control signal.
Check for improper wiring hook-up.
If humidity controller or transmitter are out of calibration
or malfunctioning, repair or recalibrate.
If zone valve end switch is not opening, repair or replace.
If aquastat is malfunctioning and heaters are locked in,
check for 24 VAC return from aquastat.
Check if SCR shorted. Repair or replace as needed.
HUNTING (humidity
swings above and
below desired set
point)
Malfunctioning control
system
If there is a faulty or inaccurate humidity controller or
transmitter, repair or replace.
Check for proper VAPOR-LOGIC control settings: RH
set point, HL set point, throttling range, cycle rate, delay
time settings, PID tuning, etc.
Relocate poorly located control components. (See
humidity control placement drawing on page 5 for
recommendations.)
If inappropriate control components are being used,
change components.
If inappropriate control components are being used,
change components.
On SCR units: Control wire and power wires must be
physically separated from each other. If they are not, an
induced control voltage may occur, causing erratic
operation.
®