TROUBLE-SHOOTING GUIDE
PROBLEM POSSIBLE CAUSE RECOMMENDED ACTION
CONTROL DOES
NOT ENERGIZE
Non-existent supply voltage to
unit
Check main line fuse.
Check main line safety switch.
Check heater fuses.
Non-existent control voltage Check for proper supply.
Verify proper transformer voltage characteristics.
Verify proper wiring of transformer.
Check for control circuit voltage, 24 VAC. If voltage is no
present, check transformer circuit breaker. Reset if
needed.
Heater over-temperature
thermostat open (optional)
Reset manual switch located above heater.
UNIT DOES NOT
FILL WITH WATER
Malfunctioning fill valve First, disconnect brown wire and then the orange wire
from VAPOR-LOGIC board terminals 1 & 2 of terminal
block J12. Fill valve should open.
If fill valve does not open, verify proper 24 VAC
(terminals 20 & 21) to fill valve. If voltage is present and
valve does not open, replace valve or valve coil.
Verify that coil is 24 VAC.
Verify that valve stem moves freely.
No water supply to fill valve Check if water supply line strainer is plugged.
Verify that manual water line shut-off valve is open and
that pressure exists.
Improper slide switch setting on
VAPOR-LOGIC control board
Set slide switch to "AUTO" mode.
VAPOR-LOGIC control is in
"end of season" drain mode
Check for humidity demand. (VAPOR-LOGIC control
board terminals 5, 6 & 7 - Control Input 1 of terminal
block J8.)
Malfunctioning level control
system
Verify that unit has new probe head design. If probe
head does not have skirt extensions surrounding probe
rods, it is an obsolete model and DRI-STEEM
recommends replacement of probe assembly.
®