TROUBLE-SHOOTING GUIDE
PROBLEM POSSIBLE CAUSE RECOMMENDED ACTION
UNIT DOES NOT
FILL WITH WATER
(con't.)
Malfunctioning level control
system (con't.)
Disconnect brown and orange wires connected to
VAPOR-LOGIC board terminals 1 & 2 of terminal block
J12. If fill valve does not open, check for proper 24 VAC
(terminals 20 & 21) to fill valve coil. If proper voltage is
not present, the control board is defective.
Check terminals 1, 2, 3 & 4 on VAPOR-LOGIC control
board terminal block J12 for correct voltage:
3 (purple) to 4 (yellow), no water present > 2 VAC. 3
(purple) to 4 (yellow), water present < 0.25 VAC. 2
(orange) to 4 (yellow), same readings as above. 1
(brown) to 4 (yellow), same readings as above.
FILL VALVE DOES
NOT CLOSE
Open drain valve If automatic drain valve is locked in manual open
position, reset to automatic.
Replace valve if there is a broken return spring on the
drain valve.
Clean or replace drain valve if an obstruction in the valve
will not allow complete closure.
Close manual drain valve, if it is open.
If VAPOR-LOGIC shorted output to fill valve coil, replace
board.
Malfunctioning level control
system
Check if probe head is fully plugged in.
If needed, clean probe rod tips.
Verify that VAPOR-LOGIC control board terminal 4 is
grounded.
If there is low water conductivity, add salt to tank water. (I
this solves the problem, consult DRI-STEEM for further
advice.)
Replace board if VAPOR-LOGIC control board is
defective.
Verify that slide switch is set to "AUTO" mode.
Verify that probe is wired correctly.
Check terminals 1, 2, 3 & 4 on VAPOR-LOGIC control
board terminal block J12 for correct voltage: 3
(purple) to 4 (yellow), no water present > 2 VAC. 3
(purple) to 4 (yellow), water present < 0.25 VAC. 2
(orange) to 4 (yellow), same readings as above. 1
(brown) to 4 (yellow), same readings as above.
®