P a g e 5 8 D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e P a g e 5 9
H u m i d i f i c a t i o n s y s t e m c o m p o n e n t s
p l a c e m e n t
Determine humidifier placement
A humidification system generally consists of a vapor or steam
generator and a dispersion assembly. The proper placement of
these two components is crucial for successful system operation.
Usually, there is no single correct placement for a humidifier. Much
depends on system design and application. However, the following
paragraphs and dispersion assembly placement examples are
presented as guidelines for common situations.
First, check available absorption distance
Available absorption distance affects system choice. Dispersed
steam must be absorbed into the airflow before it comes in contact
with any duct elbows, fans, vanes, filters, or any object that can
cause condensation and dripping. Not all humidification systems
guarantee absorption within a short distance, so it is important to
be aware of the available absorption distance early in your design
process.
Placing a dispersion assembly in an AHU
(see Figure 59-1)
Location A is the best choice. Installing
downstream of heating and cooling
coils provides laminar flow through
the dispersion unit; plus, the heated
air provides an environment for best
absorption. Use a multiple tube dispersion
unit to ensure complete absorption of
steam vapor before fan entry.
Location B is the second-best choice.
However, in change-over periods, the
cooling coil will eliminate some moisture
for humidification.
Location C is the third-best choice. Air
leaving a fan is usually very turbulent
and may cause vapor to not absorb at
the expected absorption distance. Allow
for more absorption distance if installing
downstream of a fan.
Location D is the poorest choice. The
cooler air at this location requires an
increased absorption distance.
Outside air
Relief air
Preheat coil
Motorized
air dampers
Supply airow
Filters
Economizer
control device
Heating coil
Cooling coil
8' to 12' (2.4 m to 3.7 m)
Duct high limit humidity control
for dispersion locations A, B
Airow proving switch
Dispersion discharges against
airow
Airow proving
switch
Duct high limit humidity
control for dispersion location C
Return airow
8' to 12'
(2.4 m to 3.7 m)
3' to 5'
(1 m to 1.5 m)
Fan
Figure 59-1:
Placing a dispersion assembly in an AHU
ABD
C
Exterior
building wall