Aquastat set point feature
Note: This feature is not applicable for XT humidifiers.
The aquastat set point is the minimum tank temperature the
Vapor-logic4 controller maintains when there is no call for
humidity or when safety circuits are not satisfied (e.g., high limit or
airflow proving switch). The aquastat set point is adjusted through
the water management section of the Setup menu. This feature
shortens the tank preheat time, providing a rapid response to a call
for humidity.
For example, if the aquastat is set at 180 °F (82 °C) when a call for
humidity occurs, the tank only needs to warm up 32 °F (18 °C) to
reach the boiling point. However, if the aquastat is at its minimum
default setting of 40 °F (4 °C) and the tank is in an average-
temperature occupied room, when a call for humidity occurs, the
tank needs to warm up from room temperature to the boiling point
before producing steam. When an aquastat call is heating the tank,
the word “Heating” appears on the Home screen. Aquastat heating
will occur with high-limit and airflow alarm conditions.
Freeze protection
Freeze protection is similar to aquastat operation with some
exceptions. The freeze protect set point is fixed at 40 °F (4 °C). Its
purpose is to prevent the tank from freezing in cold environments.
Unlike aquastat, if a condition exists that prevents the heaters,
burners, and valves from firing (such as an alarm, an external
interlock switch is open, or the humidifier is in Standby mode),
instead of remaining idle, the controller switches to manual drain
run mode and the tank drains to prevent freezing. Change mode to
Auto to resume operation.
When the tank is heating to prevent freezing, the word “Heating”
appears on the Home screen. When the tank is draining or has
drained to prevent freezing, the “Freeze drain” message appears
in the Messages Log and the Message softkey label becomes
highlighted.
Fan-based dispersion operation
If your humidifier is equipped with a Space Distribution Unit
(SDU) or an Area-type fan, it is enabled after the Vapor-logic4
controller receives a call for humidity and the tank water is
approaching boiling temperature.
When the humidifier no longer receives a call for humidity, it stops
heating and the SDU or Area-type fan continues to run for the
time delay period (as defined in the fan-based dispersion section
Setup menu).
0QUJPOTBOEGFBUVSFT
Operation