Table 30-1:
Setup menu (continued)
Menu item
Default
value
Minimum
value
Maximum
value
Units Notes
Programmable outputs
Dry contact --------
$"65*0/
1SPHSBNNBCMFESZDPOUBDUNBYJNVNDVSSFOU
Programmable dry contact (P12) is rated for 24 VAC,
10 Amp maximum. Exceeding this maximum rating
can cause the dry contact (relay) component or the
Vapor-logic4 board to fail.
All alarms Yes No Yes -- A dry contact activates whenever there is an alarm.
Selected alarms/messages No No Yes --
A dry contact activates whenever there are alarms or
messages selected from the setup list.
Heat on-off enabled No No Yes -- A dry contact activates when the humidifier is heating.
Steam yes-no enabled
(not an XT menu item)
No No Yes --
A dry contact activates when the tank temperature
reaches boiling.
24 VAC triac --------
$"65*0/
1SPHSBNNBCMFUSJBDNBYJNVNDVSSFOU
Programmable triac (P16) is rated for 100 mA from
the factory, and up to 4 Amps when a 24 VAC, 4 Amp
(100 VA) transformer is wired in parallel to the factory
transformer. Exceeding this maximum rating can cause
the triac component or the Vapor-logic4 board to fail.
All alarms No No Yes -- A triac activates whenever there is an alarm.
Selected alarms/messages No No Yes --
A triac activates whenever there are alarms or
messages selected from the setup list.
Heat on-off enabled No No Yes -- A triac activates when the humidifier is heating.
Steam yes-no enabled
(not an XT menu item)
No No Yes --
A triac activates when the tank temperature reaches
boiling.
Set date and time
Date -- 1/1/2007 1/1/2099 mm/dd/yy
Time -- 0:00 23:59 Hours:Minutes 24 hour clock
Language
Display in English -- No Yes --
Select one language for both keypad/display and Web
interface communications.
Display in French -- No Yes --
Display in German -- No Yes --
Display in Spanish -- No Yes --