Table 30-1:
Setup menu (continued)
Menu item
Default
value
Minimum
value
Maximum
value
Units Notes
Units
Display inch-pound -- No Yes --
Display SI -- No Yes --
Security
Require password No No Yes --
Set password None 0 9999 -- Enter a four-digit password using numbers only.
Time-out 5 1 120 Minutes
The number of inactivity minutes Vapor-logic4 remains
in read-write mode before returning to read-only mode
Capacity adjust
Capacity calibration (GTS systems) 100.0 0.0 245.0 %
Changing the capacity calibration setting changes
reported, not actual, humidifier output.
Capacity calibration (XT systems) 100.0 10.0 100.0 %
Changing the capacity setting changes the actual
humidifier output.
Idle time
Idle time 5 1 120 Minutes
Select number of minutes keypad/display remains idle
before returning to the Home screen.
Reset to defaults
Reset to defaults --------
$"65*0/
5IJTBDUJPODBOOPUCFSFWFSTFE
Select this if you want to reset all humidifier settings to
factory defaults
Valve span
Span
Min 2.00
Max 10.00
0.00 10.00 VDC
4UFQo4FUVQ
Installation