D R I - S T E E M V a p o r m i s t h u m i d i f i e r P a g e 2 3
Table 23-1:
Hose kit sizing by model
Humidifier models
Hose kit
(vapor hose, dispersion tube, and hardware)
Maximum capacity of dispersion tube
lbs/hr kg/h
VM 2-8 1½" (DN40) hose kit without drain 28.4 12.9
VM 10-16
1½" (DN40) hose kit with drain 56.8 25.8
2" (DN50) hose kit without drain 56.8 25.8
VM 21-25 2" (DN50) hose kit with drain 85.2 38.6
VM 30-34 These models require multiple tube assemblies and cannot use a hose kit.
S p a c e D i s t r i b u t i o n U n i t d i s p e r s i o n
Figure 23-1:
SDU-I mechanical detail
Humidified air
discharge grille
24.2"
(615 mm)
18.6"
(472 mm)
10.9"
(276 mm)
1½" (DN40)
steam inlet
Front view
Side view
16.1"
(409 mm)
Air intake grille
2.25"
(57 mm)
DC-1076
Figure 23-2:
SDU-E mechanical detail
Steam
outlet
24.2"
(615 mm)
18.6"
(472 mm)
10.9"
(276 mm)
1½" (DN40)
or 2" (DN50)
steam inlet
Front view
Side view
16.1"
(409 mm)
Steam inlet
2.25"
(57 mm)
DC-1078
¾" (DN20) pipe
thread drain
nipple.
See note
below.
3.2" (82 mm)
Note: The SDU-E dispersion box requires an installed condensate drain line and
water seal, provided by installer. See Figure 23-3.
Figure 23-3:
SDU-E drain line piping
Install SDU-E frame
plumb and level
Union
Elbow
1" (25 mm)
air gap
Dispersion box
¾" pipe thread (DN20)
dispersion box drain and P-trap
piping, rated for 212 °F (100 °C)
Spill funnel. Plumb to floor drain.
Open floor drain. Refer to
governing codes for drain pipe
size and maximum temperature
requirements.
OM-1245
Drain
4" (102 mm)