VAPORMIST®Electric-to-Steam HumidifierInstallation, Operation, and Maintenance ManualREAD AND SAVE THESE INSTRUCTIONS
6VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALSPECIFICATIONSOM-637-1OM-82-4-XDispersion optionsUltra-sorbRapid-sorbSingle dispersion tubeT
7VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALSelecting a location HUMIDIFIERWhen selecting a location for the humidifier, consider the fol
8VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALMounting WARNINGMounting hazardMount humidifier per the instructions in this manual and to a
9VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALTop (when SDU is not mounted directly above the Vapormist): 18"(460 mm)Right side elect
10VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONWater supply line: • 1/4" NPT (DN8) connection size• 25 to 80 psi (175
11VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALPiping:INSTALLATIONUnions by installerStrainer, by installer3/4" pipe thread (DN20) ta
12VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALPiping:INSTALLATIONSupply water piping may be of any code-approved material (copper, steel,
13VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONPiping:DC-1160DC-1138mc_050610_1345Note:Use a condensate pump rated for your ap
14VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALFused disconnect (provided by installer)Power supply (provided by installer)OM-1007Notes: •
15VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALWiringShield/screen ground lugVapor-logic keypad/displayMicroprocessor boardOM-1505Note: Fo
iiVAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WARNINGCAUTIONIndicates a hazardous situation that could result in death or serious injury
16VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONOther factors affecting humidity controlHumidity control involves more than the
17VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALssssssssINSTALLATIONDC-1084Outside airRelief airReturn airAir handling unit8' to 12&ap
18VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:High-efficiency Tube optionDispersion assemblies with the High-efficiency Tube op
19VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONDispersion:Important: Reducing the inside diameter of the steam hose or tubing
20VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:INSTALLATIONTable 20-1:Steam loss of interconnecting steam hose or tubingDescrip
21VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONDispersion:Install a drip tee as shown below when the humidifier is mounted high
22VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:MOUNTING SDU-I AND SDU-EBoth SDUs can be mounted on a wall directly above the Va
23VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONDispersion:OM-282-716"(406 mm)18.5"(470 mm)16" (406 mm)3" (
24VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:INSTALLATIONHumidified air discharge grille24.2" (615 mm)18.6"(472 mm)1
25VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONDispersion:SDU-E CONDENSATE DRAIN CONNECTION1. Piping must be minimum 3/4"
iiiVAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALWarnings and cautions WARNINGDisconnect electrical powerDisconnect electrical power befor
26VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALINSTALLATIONAs steam is discharged from the SDU-E, it quickly cools and turns to a visible
27VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:INSTALLATIONTable 27-1:SDU-E minimum nonwetting distanceskWMaximum steam capacit
28VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALSingle dispersion tubeINSTALLATION NOTES• Use a hose clamp to connect the steam outlet to
29VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDC-1449Dispersion:Single dispersion tube with condensate drainMounting nut 3/8" - 16
30VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:INSTALLATIONImportant: Before marking and drilling holes in the duct or air hand
31VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 31-1: Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb e
32VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALRapid-sorbL-bracketVapormist humidifierDuctSecure and seal escutcheon plates90° long sweep o
33VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:Note:See Page 36 for steam supply and condensate drain line connection instructi
34VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALRapid-sorbOM-73996" (152 mm) Point tubelets (steam orifices) perpendicular to airflow Du
35VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:INSTALLATIONNote:See Page 36 for steam supply and condensate drain line connecti
ivVAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable of contentsATTENTION INSTALLERRead this manual before installing. Leave manual with p
36VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALDispersion:STEAM SUPPLY CONNECTIONS TO RAPID-SORB HEADERConnect the steam supply interconne
37VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALOPERATIONPrinciple of operation1. When the system is first activated, the fill valve opens
38VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALOPERATIONIf an item in the Start-up checklist below does not apply to your system, skip to
39VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALAfter the system is installed and connected properly: 1. Verify that the humidifier, contr
40VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALTap/softened waterMAINTENANCE WARNINGHot surface and hot water hazardDo not touch the tank
41VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALOM-778-3MAINTENANCEHumidifier De-scaling SolutionScale buildup on humidifier heaters acts as
42VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUAL2. Seasonally (or as required, depending on water quality) • Remove the evaporating chamb
43VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUAL• Install the probe and probe plug assembly. Verify ground wire is solidly connected to ta
44VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALRO/DI water optionMAINTENANCERO/DI humidifiers use RO/DI water. Because these water types ar
45VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUAL2. Loosen the four cover bolts and remove the cover assembly from the tank.3. Inspect th
1VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable of contentsKeypad/display and troubleshootingThe Vapor-logic version 5 Installation an
46VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALHumidifierOM-768Tap/softened water VapormistRO/DI water VapormistREPLACEMENT PARTSFIGURE 46-
47VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALHumidifierREPLACEMENT PARTSTable 47-1:Vapormist humidifier replacements partsNo. Description
48VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALSDU-EOM-1503Table 48-1:SDU-E replacement partsNo. Description Qty. Part No.1 Shroud 1 33000
49VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALSDU-IOM-1504Table 49-1:SDU-I replacement partsNo. Description Qty. Part No.1 Shroud 1 33000
50VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALOM-213-4SubpanelTable 50-1:Vapormist subpanel with SSRNo. Description Qty. Part No. No. Des
51VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALOM-1506aTable 51-1:Vapormist subpanel with SDUNo. Description Qty. Part No.1 Subpanel, barr
Form No. VM-IOM-0913Part No. 890000-201 Rev 8FCTwo-year Limited WarrantyDriSteem Corporation (“DriSteem”) warrants to the original user that its produ
2VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALmc_071912_1545Vapormist humidifiers use heat caused by electrical resistance in submerged hea
3VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALProduct overviewOVERVIEWCONTROLLERThe Vapor-logic controller in Vapormist humidifiers provide
4VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALTable 4-1:Vapormist capacities, electrical specifications, and weightsVM modelMaximum steam
5VAPORMIST INSTALLATION, OPERATION, AND MAINTENANCE MANUALSPECIFICATIONSDC-11672" (50 mm)Venting0.50" (13 mm) hole in base for water fill lin