MAINTENANCE
Remove loose deposits and residue that falls into rear
header with a vacuum cleaner and hose extension.
Inspect 2" return tubes and clean if necessary.
Run thin brush between turbulator and tube wall on all
four sides.
Reinstall burner assemblies and gaskets; vent box
andgasket; all electrical wiring; gas train shroud; and
pressure switch connections.
2. Burner: The burner surface is a self cleaning
ceramic fabric which does not require cleaning or
maintenance.
3. INSPECTION RECOMMENDATIONS by user every
30 days. Appliance system should be inspected
once a year by a qualified service person.
Flue passageways external to the appliance such
as vent connector and chimney to be clear and
free of obstructions.
Vent connector is in place, sloping upward and is
physically sound without holes or excessive
corrosion.
Physical support of the appliance is sound without
sagging cracks, gaps...between floor stand legs
and tank flanges, or between trapeze bars and
tank bottom.
Verify there are no obvious signs of deterioration
of the appliance.
Burner flame will operate blue or orange in color -
up to a ¼" from the surface of the burner. See
figure 24-1.
See "Cleaning Water Level Probes" and "Cleaning
Low Water Cut-Out Probe" on page 23.
2 1/4" Dia. Burner
Flame may appear blue at
start-up, then turn orange
after heat-up
OM-847
When servicing or repairing this equipment, use only
DRI-STEEM approved service replacement parts. A
complete replacement parts list are on pages 26 and
27. Refer to the rating plate on the unit for complete
unit model number, serial number and company ad-
dress. Any substitution of parts or controls not ap-
proved by DRI-STEEM will be at owner's risk and will
void the warranty.
Both GTS
®
and GTS-DI
Inspecting the Burner Assemblies and Heat
Exchanger Tubes
1. Note: Soot and carbon deposits may indicate a
combustion problem that needs to be corrected.
Consult the factory.
This is not regular maintenance, but if the heat
exchanger tubes contain carbon deposits, soot or
other residue, clean as follows:
• Turn off gas, electrical power, and water supply.
Remove gas train shroud.
Disconnect wiring to blowers, flame sensors, gas
valves, and ignition controllers.
Remove burner assemblies (each assembly is
mounted with four bolts).
Remove vent box.
Use a four-inch flue brush with a 28" extension and
reversible drill. Work brush in and out of all four fire
tubes.
Figure 24-1: Burner Assembly Flame